IKA Box Condensers

You are here: Home / Cooling equipment / IKA Box Condensers

IKA Box Condensers

Heat exchangers

IKA Box Condensers

Box / U-type air-cooled condensers with top discharge — compact footprint and airflow less sensitive to prevailing wind, covering roughly 20–84 kW class rejection.

Heat rejection band
Approx. 20–84 kW (catalogue IKA range)
Air path
Box / U-type, top discharge
Fans
1–2 fans typical, Ø500–630 mm class
Tube
Internally enhanced copper (catalogue family)

Models

Dimension drawings

Tables

IKA box type — heat exchange, fans and dimensions

ModelHeat exchange (kW)Area (m²)FansFan Ø (mm)Air flow (m³/h)Motor (W)SupplyLength A (mm)Width B (mm)Height C (mm)Install D (mm)Install E (mm)
21.960150070002X205380/50Hz9257201000595687
21.96024002X45002X205380/50Hz11857401000595707
29.28024502X54002X250380/50Hz12257401100635707
36.510025002X70002X414380/50Hz1390760900800730
43.812025002X70002X414380/50Hz1470850950880820
47.513025002X70002X414380/50Hz14708701000880840
51.114025002X70002X414380/50Hz14908701050900840
54.815025502X90002X600380/50Hz14908901100900860
65.718026302X120002X800380/50Hz163092511001040890
73.020026302X120002X800380/50Hz163092512001040890
84.023026302X120002X800380/50Hz167099514001080960

Cards

Product description

IKA box condensers are compact, top-blow air-cooled units for sites where pad space is tight or side wind would disturb a horizontal face. Catalogue models (IKA-60N501 through IKA-230N632 class) list heat exchange, coil area, fans, airflow, motor power, overall dimensions and install width.

Top discharge keeps exhaust clear of adjacent walls; the box envelope is easier to place beside plant rooms or on small roofs. Construction matches the catalogue copper-tube family with ~3.0 MPa class pressure testing. Select on required kW and available install width from the table.

Applications

  • Small outdoor pads and roof plant
  • Cold rooms beside occupied buildings
  • Sites where wind direction limits side-blow condensers
  • Compact commercial refrigeration packs

Features

Top discharge

Upward airflow reduces sensitivity to prevailing wind compared with side-blow banks.

Compact box footprint

Short plan dimensions with published install width for tight pads and roofs.

Practical capacity band

Roughly 20–84 kW heat exchange across the published IKA range.

Serviceable fans

Fan diameter, airflow and motor power listed for electrical design and spares.

Technical properties

Heat rejection band
Approx. 20–84 kW (catalogue IKA range)
Air path
Box / U-type, top discharge
Fans
1–2 fans typical, Ø500–630 mm class
Tube
Internally enhanced copper (catalogue family)
Pressure test
~3.0 MPa class (catalogue)

Send required heat rejection, ambient and available pad size — we will match an IKA model and install width.

Other equipment